EM-M17b converts applied frequency to 0...10 V or to 4...20 mA signal. Frequency range is selectable with DIP-switches. Converter can be used with most of the commonly available transducer types. Frequency can be applied also as a pulsed voltage signal. The frequency input can be isolated optically if transducer supply and SW1/1 is left open. Converted signal is filtered using a 2nd order filter so that the ripple of the incoming frequency is efficiently attenuated. The output of EM-M17b is both short circuit and overload protected. Operating voltage range is wide and the supply is protected against incorrect polarity.


 

TECHNICAL DATA

Operating Voltage20...32 Vdc
Current Consumption50 mA max.
Linearity Error0.1 % typical
Thermal Drift< 100 ppm/°C
Transducer Supply15 Vdc / 8.5 Vdc (NAMUR)
Input SettingsOpen collector NPN / Open collector PNP / NAMUR / Pulse (isolated)
Input Range4...25 V
Input Impedanceapprox. 2 kΩ
Frequency Ranges0...200, 500, 1000 Hz