ELECTROMEN – MOTOR CONTROLLER TROUBLESHOOTING GUIDE

This troubleshooting guide provides practical steps for identifying common problems in Electromen motor controller applications.

Some problems and diagnostic procedures are different for Brushed DC motors and Brushless DC motors (BLDC). Where relevant, the instructions below clearly identify the motor type.

Important: Product features, protection functions, parameter numbers and electrical ratings vary between Electromen products. Always refer to the product-specific datasheet and user manual.

Select a Motor Type or Application

Common Problems

  1. Motor Does Not Start
  2. Motor Runs Roughly or Irregularly
  3. Motor Draws Excessive Current
  4. Motor Runs in the Wrong Direction
  5. Overcurrent / I-Trip Fault
  6. Motor Does Not Reach Target Speed
  7. Motor Stops or Resets Unexpectedly
  8. Overvoltage During Braking
  9. Controller Overtemperature
  10. Motor or Controller Becomes Too Hot
  11. Speed Control Is Unstable
  12. BLDC Hall Sensor / Commutation Problems
  13. BLDC Motor Starts Poorly in One Direction
  14. Brushed DC Motor Brush / Commutator Problems
  15. Positioning Is Unstable or Inaccurate
  16. Homing or Learning Does Not Complete
  17. Analog Control Input Problems
  18. Digital Input Does Not Work as Expected
  19. Modbus Communication Problems
  20. Fault Output / Status Indication Problems

1. Motor Does Not Start

Common Checks – Brushed DC and BLDC

  • Verify that the controller supply voltage is present and within the specified range.
  • Check the external supply fuse.
  • Verify Start/Stop, Disable and Shutdown input states.
  • Check that the speed command is above the minimum operating level.
  • Verify the current limit setting.
  • Check motor and supply wiring.
  • Check whether a fault condition is active.
  • Check that the mechanical system is free to move.

Additional Checks – Brushed DC Motor

  • Measure continuity through the motor.
  • Check brushes and commutator if accessible.
  • Check for worn brushes or poor brush contact.

Additional Checks – BLDC Motor

  • Check all three motor phase connections.
  • Check Hall sensor supply and ground.
  • Verify all three Hall signals.
  • Check Hall sensor and motor phase phasing.

Diagnostic hint: A BLDC motor that does not start but draws significant current often indicates an incorrect or missing Hall signal, incorrect phase/Hall combination or a mechanically blocked motor.

↑ Back to Troubleshooting Guide


2. Motor Runs Roughly or Irregularly

Brushed DC Motor

Check:

  • Supply voltage stability
  • Current limit setting
  • Mechanical load
  • Motor brushes
  • Commutator condition
  • Loose motor connections

A worn brush or damaged commutator can cause irregular torque, electrical noise and unstable operation.

BLDC Motor

Rough operation combined with unusually high current is a strong indication that the motor phase sequence and Hall sensor sequence may not correspond.

Check:

  • Motor phases U/V/W
  • Hall signals A/B/C
  • Hall sensor supply voltage
  • Missing or intermittent Hall signal
  • Phase/Hall combination

Important: Do not continue operating a BLDC motor with incorrect commutation. Incorrect phasing can produce high motor and controller current.

↑ Back to Troubleshooting Guide


3. Motor Draws Excessive Current

Common Causes

  • Mechanical overload
  • Blocked or partially blocked mechanism
  • Acceleration ramp too short
  • Motor incorrectly sized for the load
  • Motor winding fault

Brushed DC Motor

Check the motor resistance, brush condition, commutator and mechanical load. A damaged armature or commutator can increase current consumption.

BLDC Motor

Incorrect Hall/phase phasing is one of the first items to check if a BLDC motor draws high current while producing poor torque or rough rotation.

Recommended Test

  1. Reduce the current limit.
  2. Remove the mechanical load if possible.
  3. Run at low speed.
  4. Observe motor current.
  5. Compare unloaded operation with loaded operation.

↑ Back to Troubleshooting Guide


4. Motor Runs in the Wrong Direction

Brushed DC Motor

Rotation direction is determined by motor polarity. Electromen controllers normally provide electronic direction control, so use the controller Direction input or command where available.

BLDC Motor

After correct Hall and phase commutation has been established, use the controller Direction command to reverse rotation.

Do not randomly exchange BLDC phase wires to reverse direction, because the Hall sensor sequence must remain correctly matched to the phase sequence.

↑ Back to Troubleshooting Guide


5. Overcurrent / I-Trip Fault

I-Trip indicates that motor current has remained at or above the configured current limit for longer than the permitted time.

Possible Causes

  • Mechanical overload
  • Blocked motor or mechanism
  • Acceleration ramp too short
  • Current limit incorrectly adjusted
  • I-Trip delay too short for normal acceleration
  • Motor too small for the application
  • BLDC Hall/phase mismatch

Diagnostic Procedure

  1. Check whether the mechanism moves freely.
  2. Check motor current without mechanical load where possible.
  3. Verify current limit setting.
  4. Increase acceleration time if the current peak occurs during starting.
  5. Verify the I-Trip delay.
  6. For BLDC motors, verify Hall and phase wiring.

Do not increase the current limit simply to eliminate an I-Trip fault without first identifying why excessive current is present.

↑ Back to Troubleshooting Guide


6. Motor Does Not Reach Target Speed

Possible Causes

  • Supply voltage too low
  • Current limit active
  • Mechanical load too high
  • Incorrect speed input scaling
  • Maximum speed parameter limiting the command
  • Motor Back EMF approaching available supply voltage
  • Incorrect closed-loop speed settings

Check

Measure the supply voltage while the motor is operating. A supply that appears correct without load may drop significantly when motor current increases.

If the controller is operating at the current limit, the motor may not have sufficient available torque to accelerate to the requested speed.

↑ Back to Troubleshooting Guide


7. Motor Stops or Resets Unexpectedly

Check for:

  • Undervoltage
  • Overvoltage
  • Overtemperature
  • I-Trip
  • Disable input activation
  • Shutdown input activation
  • Loose power connection
  • Insufficient power supply capacity
  • EMC interference

Measure the DC supply directly at the controller during acceleration, deceleration and direction changes. Short voltage disturbances may not be visible when measuring only the unloaded supply.

↑ Back to Troubleshooting Guide


8. Overvoltage During Braking

When a motor decelerates, mechanical energy can be returned to the DC supply. This is called regenerative braking.

Typical Causes

  • Stop ramp too short
  • High-inertia load
  • Power supply unable to absorb regenerative energy
  • Braking resistor missing
  • Incorrect braking resistor
  • Incorrect braking activation level

Battery Supply

A suitable battery may absorb regenerative energy, provided that the battery, BMS and charging system permit reverse charging current.

Standard DC Power Supply

Many standard DC power supplies cannot absorb reverse current. Regenerative energy can therefore raise the DC bus voltage.

Corrective Actions

  • Increase the stop ramp time.
  • Check braking resistor operation.
  • Verify resistor value and power rating.
  • Verify the braking activation threshold.
  • Check the inertia and braking requirements of the application.

↑ Back to Troubleshooting Guide


9. Controller Overtemperature

Possible Causes

  • Continuous current too high
  • Insufficient cooling
  • High ambient temperature
  • Poor thermal contact to mounting surface
  • Repeated acceleration and braking
  • Motor operating continuously near current limit

Check

  • Actual motor current
  • Ambient temperature
  • Airflow
  • Mounting surface
  • Cooling fan operation where applicable

The controller current rating must always be considered together with the specified cooling conditions.

↑ Back to Troubleshooting Guide


10. Motor or Controller Becomes Too Hot

Motor copper losses increase approximately with the square of current:

PLOSS ≈ I2 × R

A relatively small increase in motor current can therefore cause a significant increase in heating.

Check:

  • Continuous motor current
  • Current limit setting
  • Mechanical load
  • Acceleration frequency
  • Motor cooling
  • Controller cooling

Additional BLDC Check

Incorrect commutation can cause excessive heating even when mechanical output power is low. Check Hall and phase phasing if the BLDC motor runs hot and roughly or draws unexpectedly high current.

↑ Back to Troubleshooting Guide


11. Speed Control Is Unstable

Open-Loop Control

In open-loop operation, motor speed can change with load and supply voltage. Some variation is therefore normal.

Closed-Loop Control

Check:

  • Speed feedback signal
  • Feedback scaling
  • Motor pole count where applicable
  • Control parameters
  • Mechanical backlash or oscillation

Analog Speed Command

If the speed command itself is unstable, check:

  • Analog input voltage
  • Signal ground
  • Input scaling
  • Cable routing
  • Electrical noise

↑ Back to Troubleshooting Guide


12. BLDC Hall Sensor / Commutation Problems

This section applies specifically to BLDC motors.

Typical Symptoms

  • Motor does not start
  • Motor vibrates
  • Motor runs roughly
  • Motor current is unusually high
  • Motor has poor torque
  • Operation differs between directions

Check Hall Signals

A typical sensored BLDC motor uses three Hall signals. During rotation, the Hall states should change in a valid sequence.

Check:

  • Hall supply voltage
  • Hall ground
  • Hall A signal
  • Hall B signal
  • Hall C signal
  • Connectors and wiring

Phase/Hall Phasing

The three motor phase wires and three Hall signals must form a compatible commutation combination.

If the motor runs roughly or draws high current after wiring changes, stop the motor and verify the combination before continuing.

↑ Back to Troubleshooting Guide


13. BLDC Motor Starts Poorly in One Direction

This section applies specifically to BLDC motors.

Possible Causes

  • Incorrect Hall/phase phasing
  • One Hall signal missing or intermittent
  • Mechanical load differs between directions
  • Mechanical backlash or binding
  • Insufficient starting current

If electrical performance is clearly different between forward and reverse operation, verify the Hall signals and commutation phasing before adjusting current limits.

↑ Back to Troubleshooting Guide


14. Brushed DC Motor Brush / Commutator Problems

This section applies specifically to brushed DC motors.

A brushed DC motor performs commutation mechanically using brushes and a commutator.

Typical Symptoms

  • Intermittent starting
  • Irregular motor speed
  • Excessive electrical noise
  • Reduced torque
  • Motor stops at certain rotor positions
  • Visible excessive sparking

Check:

  • Brush wear
  • Brush spring pressure
  • Brush movement in holders
  • Commutator condition
  • Motor connections
  • Armature continuity

Motor brush and commutator faults cannot normally be corrected by changing controller parameters.

↑ Back to Troubleshooting Guide


15. Positioning Is Unstable or Inaccurate

Possible Causes

  • Dead zone too small
  • Braking area incorrectly adjusted
  • Load compensation too high
  • Mechanical backlash
  • High friction
  • Mechanical elasticity
  • Insufficient feedback resolution
  • Incorrect position scaling

If the Motor Oscillates Around the Target

Check the dead zone, braking area and load compensation. Also inspect the mechanical system for backlash and elasticity.

If the Motor Consistently Stops Before the Target

Check whether friction is preventing final movement or whether the braking area is too large.

If the Motor Overshoots

Check braking area, approach speed, mechanical inertia and load compensation.

↑ Back to Troubleshooting Guide


16. Homing or Learning Does Not Complete

Check:

  • Motor direction
  • Position feedback
  • Mechanical end positions
  • Current limit
  • Homing speed
  • Mechanical obstruction

If the controller detects a mechanical end using motor current, the current limit and mechanical load must allow reliable end detection.

For systems using external limit or reference signals, verify the state and polarity of those signals.

↑ Back to Troubleshooting Guide


17. Analog Control Input Problems

Typical Symptoms

  • Motor does not respond to speed command
  • Full speed cannot be reached
  • Motor starts before expected command level
  • Speed fluctuates

Check:

  • Actual voltage at the controller input
  • Signal ground connection
  • Selected input range
  • Minimum and maximum scaling parameters
  • Control source output impedance
  • Electrical noise

Measure the control voltage directly between the controller analog input and its signal ground.

↑ Back to Troubleshooting Guide


18. Digital Input Does Not Work as Expected

Check:

  • Input wiring
  • Input voltage level
  • Input polarity
  • Parameter-selected input function
  • Higher-priority inputs such as Disable
  • Local / Bus operating mode

Many Electromen products allow digital input functions to be changed by parameters. Always verify what function is currently assigned to the input.

If several commands are active simultaneously, check the input priority described in the product manual.

↑ Back to Troubleshooting Guide


19. Modbus Communication Problems

No Communication

Check:

  • RS-485 A/B wiring
  • Signal ground
  • Device address
  • Baud rate
  • Parity
  • Stop bits
  • Correct Modbus register

Communication Is Intermittent

Check:

  • Bus termination
  • Linear bus topology
  • Long branches
  • Cable quality
  • Ground potential differences
  • EMC interference

Errors Occur When the Motor Runs

This strongly suggests checking EMC installation.

  • Separate RS-485 from motor wiring.
  • Use twisted-pair cable.
  • Check shielding and grounding.
  • Check bus termination.

Recommended Test

Start troubleshooting with one controller and a short RS-485 cable. Once communication works reliably, add other devices one at a time.

↑ Back to Troubleshooting Guide


20. Fault Output / Status Indication Problems

Check the Output Type

Many Electromen status outputs are transistor outputs such as NPN open collector outputs. They do not behave like voltage-source outputs.

Verify:

  • Output type
  • External supply
  • Load connection
  • Maximum output voltage
  • Maximum output current
  • Parameter-selected output function

Output Function

On configurable products, the same output may be assigned to indicate different conditions such as:

  • General fault
  • Overcurrent
  • I-Trip
  • Speed pulse
  • Brake control

Verify the output configuration before assuming that the output itself is faulty.

↑ Back to Troubleshooting Guide


Quick Fault Identification

Symptom Brushed DC – Check First BLDC – Check First
Motor does not start Supply, commands, brushes, motor wiring Supply, commands, Hall signals, phase wiring
Motor runs roughly Brushes, commutator, load, supply Hall/phase phasing
High motor current Mechanical load, motor condition Hall/phase phasing, mechanical load
Poor starting torque Current limit, supply, motor Current limit, Hall phasing, supply
I-Trip during acceleration Load, ramp, current limit Load, ramp, current limit, phasing
Overvoltage during stop Regeneration, stop ramp, braking resistor Regeneration, stop ramp, braking resistor
Controller overheats Current and cooling Current, cooling and correct commutation
Speed fluctuates Supply, command signal, load Feedback, Hall signals, command signal

↑ Back to Troubleshooting Guide


Before Contacting Electromen Support

Providing the following information can significantly speed up troubleshooting:

  • Electromen controller model
  • Controller software or version information, if applicable
  • Motor type: Brushed DC or BLDC
  • Motor manufacturer and model
  • Motor nominal voltage
  • Motor nominal current
  • DC supply voltage
  • Measured motor current during the problem
  • Mechanical load description
  • Current parameter settings
  • Fault LED or fault output indication
  • Wiring diagram or clear photograph of the wiring

For BLDC Applications, Also Provide

  • Number of motor poles or pole pairs, if known
  • Hall sensor supply voltage
  • Hall sensor wiring information
  • Motor phase wiring information

For Modbus Applications, Also Provide

  • Modbus device address
  • Baud rate
  • Parity and stop bits
  • Function code and register being accessed
  • Master device or software being used
  • Description of the RS-485 network

A clear description of what was expected to happen and what actually happened is often one of the most useful pieces of troubleshooting information.


Safety and Product-Specific Information

This troubleshooting guide provides general engineering guidance and does not replace product-specific technical documentation.

Disconnect or isolate power before changing wiring where required. Motor controllers can produce high currents, unexpected motor movement and hot components. Braking resistors can reach high surface temperatures.

Electrical ratings, protection thresholds, parameter numbers, I/O functions, Hall sensor interfaces and communication settings vary between Electromen products.

Always refer to the datasheet and user manual of the specific Electromen controller before changing wiring or parameters.

Electromen motor controllers are components intended for integration into a complete machine or system. The system designer or integrator is responsible for correct installation and for compliance of the complete system with applicable electrical, EMC and safety requirements.

↑ Back to Troubleshooting Guide

AAA - credit rating

ISO-certified suppliers and subcontractors

100% Finnish production chain

Device design, programming, and laboratory testing

Short delivery time

Takaisin ylös
Sivustomme käyttää evästeitä käyttäjäkokemuksen parantamiseksi. Voit muuttaa eväste valintojasi asetuksista
1 Tuotetta ostoskorissa
Ostoskori
Yhteensä:
0,00€