ELECTROMEN – APPLICATION NOTES

Practical engineering guides for selecting, installing and configuring Electromen motor controllers. These application notes provide general guidance for common motor control applications and help explain the practical use of features found in Electromen products.

Note: Product features, electrical ratings and parameter settings vary between models. Always refer to the product-specific datasheet and user manual before installation or commissioning.

Application Notes


1. How to Select the Correct Motor Controller

Selecting a motor controller requires more than matching only the supply voltage and motor current. The controller must also match the motor type, starting torque, peak current, braking requirements, feedback method, control signals and thermal conditions of the application.

1.1 Identify the Motor Type

First determine whether the motor is:

  • Brushed DC motor
  • Brushless DC motor (BLDC)
  • BLDC motor with Hall sensor feedback
  • Motor used in a positioning application

The motor type determines the required power stage and feedback method.

1.2 Check the Supply Voltage

The controller supply voltage range must match the available DC supply. Always consider the maximum possible supply voltage, including ripple and voltage rise during regenerative braking.

1.3 Determine Continuous Current

The controller continuous current rating should be sufficient for the motor current during normal operation.

Continuous current capability depends on cooling, ambient temperature and installation conditions.

1.4 Determine Peak Current

Motor current can be significantly higher during:

  • Starting
  • Rapid acceleration
  • Direction changes
  • Mechanical overload
  • Positioning against a high load

The controller should therefore be selected according to both continuous and short-term peak current requirements.

1.5 Consider Braking Requirements

If the application requires rapid stopping or frequent direction changes, determine whether regenerative braking is required.

With a standard DC power supply, regenerative energy may require an external braking resistor. With a battery supply, the battery system may be able to absorb the returned energy.

1.6 Select the Required Control Method

Typical control methods include:

  • Analog speed control
  • Digital start/stop and direction inputs
  • Preset speeds
  • RS-485 Modbus control
  • Positioning control

1.7 Determine Feedback Requirements

Open-loop speed control may be sufficient for simple applications. Closed-loop control should be considered when accurate speed or position control is required.

1.8 Check Cooling and Installation

High-current applications may require:

  • A suitable metal mounting surface
  • Additional heatsinking
  • Forced-air cooling
  • Reduced current at high ambient temperature

Quick Selection Checklist

Requirement Check
Motor type DC / BLDC / Hall feedback / Positioning
Supply voltage Nominal and maximum voltage
Continuous current Normal operating current
Peak current Starting and acceleration current
Braking Freewheel / Dynamic / Regenerative
Control method Analog / Digital / Modbus
Feedback Open-loop / Hall / Position feedback
Cooling Ambient temperature and mounting

Important: Always verify the final controller selection from the product-specific datasheet and user manual.

↑ Back to Application Notes


2. How to Size a Braking Resistor

A braking resistor is used when regenerative braking returns energy to the DC supply and the power source cannot absorb that energy. The resistor converts the returned electrical energy into heat.

2.1 When Is a Braking Resistor Needed?

A braking resistor may be required when:

  • The motor decelerates rapidly.
  • The load has high inertia.
  • The application changes direction frequently.
  • The DC power supply cannot absorb reverse energy.
  • The DC bus voltage rises excessively during braking.

2.2 Braking Energy

The rotational energy stored in the load can be estimated by:

E = 1/2 × J × ω2

where:

  • E = stored energy [J]
  • J = total rotational inertia [kgm2]
  • ω = angular speed [rad/s]

Higher speed has a particularly strong effect because the stored energy increases with the square of speed.

2.3 Resistor Power

Instantaneous resistor power can be estimated using:

P = V2 / R

where:

  • P = resistor power [W]
  • V = voltage across the resistor [V]
  • R = resistance [Ω]

2.4 Example

With a braking voltage of 30V and a 10Ω resistor:

P = 302 / 10 = 90W

This is the instantaneous power. The resistor does not necessarily need to be rated continuously for this power if braking occurs only for short periods. The resistor must, however, be capable of handling the required pulse energy.

2.5 Duty Cycle

The average braking power depends on how frequently braking occurs:

PAVG = EBRAKE × braking cycles per second

The resistor must tolerate:

  • Peak braking power
  • Total energy per braking event
  • Braking duration
  • Braking frequency
  • Average thermal load

2.6 Practical Selection Procedure

  1. Determine the maximum DC bus voltage allowed by the controller.
  2. Determine the braking resistor activation voltage.
  3. Use the resistor value recommended for the controller.
  4. Estimate the peak braking power.
  5. Estimate the braking energy per stop.
  6. Determine braking frequency and average power.
  7. Select a resistor with sufficient pulse-energy and thermal capability.

Important Considerations

  • Do not use a resistor value below the minimum permitted by the controller.
  • Provide sufficient ventilation around the resistor.
  • The resistor surface temperature can become very high.
  • High-inertia systems may require a longer stop ramp.

Important: Always use the resistor range and braking threshold specified in the product-specific Electromen documentation.

↑ Back to Application Notes


3. BLDC Motor Wiring and Hall Sensor Phasing

Correct phase and Hall sensor wiring is essential for smooth and efficient operation of a sensored BLDC motor.

A typical BLDC motor has:

  • Three motor phase wires
  • Three Hall sensor signals
  • Hall sensor supply
  • Hall sensor ground

3.1 Why Correct Phasing Matters

The controller switches the three motor phases according to the rotor position reported by the Hall sensors. The Hall sequence and motor phase sequence must therefore correspond correctly.

3.2 Symptoms of Incorrect Wiring

Incorrect phase or Hall wiring can cause:

  • Rough motor operation
  • High motor current
  • Poor starting torque
  • Motor vibration
  • Incorrect rotation direction
  • Motor not starting
  • Current limit or I-Trip activation

3.3 Recommended Test Procedure

  1. Disconnect the mechanical load if possible.
  2. Set a conservative current limit.
  3. Use a low speed command.
  4. Check whether the motor starts smoothly.
  5. Observe motor current and sound.
  6. If operation is rough, stop immediately.
  7. Change the Hall sensor or phase sequence systematically.
  8. Repeat until smooth operation is achieved.

3.4 Do Not Use High Current During Testing

Incorrect Hall phasing can cause very high motor current even at low mechanical load. Initial wiring tests should therefore always be performed with a reduced current limit.

3.5 Rotation Direction

Motor direction should normally be changed using the controller direction command after correct commutation phasing has been established.

Changing only two motor phase wires without making corresponding Hall changes may result in incorrect commutation.

3.6 Hall Sensor Supply

Verify the Hall sensor voltage requirement before connection. Incorrect sensor supply voltage can damage the Hall sensors.

Practical Troubleshooting

Symptom Possible Cause
Motor does not start Incorrect Hall sequence, missing Hall signal or phase wiring error
Motor runs roughly Hall and phase sequence mismatch
Very high current Incorrect commutation phasing or mechanical blockage
Wrong direction Direction command or phasing configuration
Runs only at some rotor positions Missing or incorrect Hall sensor signal

Important: Motor manufacturers do not always use identical wire colours or Hall sensor naming. Always verify the motor documentation when available.

↑ Back to Application Notes


4. Current Limit vs. I-Trip

Current Limit and I-Trip are related functions, but they serve different purposes. Understanding the difference is important when commissioning a motor controller.

4.1 Current Limit

Current Limit restricts the maximum motor current while allowing operation to continue.

Because motor torque is approximately proportional to current:

T ≈ kT × I

the current limit also acts as an approximate torque limit.

4.2 I-Trip

I-Trip is a protective shutdown function.

If the motor current remains at or above the current limit for longer than the configured trip delay, the controller stops the motor and generates a fault.

A simplified condition is:

I ≥ ILIMIT for t > tTRIP

4.3 Main Difference

Function Current Limit I-Trip
Purpose Control motor current Protect against prolonged overload
Motor continues running Normally yes No, after trip
Affects torque Yes Indirectly
Uses delay No Typically yes
Requires reset after activation No Usually yes

4.4 Example: Normal Starting

A motor may temporarily reach the current limit during acceleration. If the acceleration finishes before the I-Trip delay expires, the motor continues to operate normally.

4.5 Example: Mechanical Jam

If the motor is mechanically blocked, the controller may remain continuously at the current limit. I-Trip can then shut the system down after the configured delay.

4.6 Setting the Current Limit

The current limit should consider:

  • Motor continuous current
  • Motor permissible peak current
  • Required starting torque
  • Controller current rating
  • Mechanical system requirements

4.7 Setting the I-Trip Delay

The delay should be long enough to allow normal starting and acceleration, but short enough to protect the motor and mechanics from prolonged overload.

Common Problems

Problem Possible Adjustment or Check
Trips immediately during normal start Check load, current limit and I-Trip delay
Motor has insufficient torque Check whether current limit is too low
Motor remains stalled without shutdown Check whether I-Trip is disabled
Frequent I-Trip faults Check mechanical load, acceleration ramp and motor sizing

Important: The exact relationship between Current Limit and I-Trip varies between Electromen products. Refer to the product-specific parameter descriptions.

↑ Back to Application Notes


5. RS-485 Modbus Wiring Guide

RS-485 is widely used for Modbus RTU communication because it provides reliable differential communication in industrial environments and allows multiple devices to share the same bus.

5.1 Basic RS-485 Signals

A typical connection includes:

  • A
  • B
  • Signal ground / GND

Always follow the terminal naming used in the product documentation.

5.2 Use a Bus Topology

RS-485 should normally be wired as a linear bus:

Master — Device 1 — Device 2 — Device 3 — Last Device

Avoid long star branches because they can cause signal reflections and communication errors.

5.3 Termination

The physical ends of a long RS-485 bus should normally be terminated with the specified termination resistance.

A commonly used RS-485 termination value is approximately 120Ω, but the product-specific instructions should always be followed.

5.4 Device Address

Each Modbus device on the same bus must have a unique address.

Two devices with the same address will cause communication conflicts.

5.5 Communication Settings

All devices communicating on the same bus must use compatible settings:

  • Baud rate
  • Parity
  • Stop bits

5.6 Ground Reference

Although RS-485 uses differential signalling, a common signal reference is recommended where required by the product documentation.

Large ground potential differences between devices should be avoided.

5.7 Cable Routing

For reliable communication:

  • Use twisted-pair cable.
  • Keep RS-485 wiring away from motor cables where practical.
  • Avoid running communication wiring parallel to high-current switching cables.
  • Use shielding where required by the installation environment.

5.8 Basic Modbus RTU Message

A Modbus RTU frame consists of:

Address | Function | Data | CRC

Common Communication Problems

Symptom Possible Cause
No communication A/B reversed, wrong address or incorrect communication settings
Communication works only occasionally Termination, cable routing or grounding problem
One device works, several do not Duplicate addresses or incorrect bus topology
Errors increase when motor runs EMC interference or incorrect cable routing
Communication fails on long cable Missing termination, wiring problem or excessive baud rate

Recommended Commissioning Order

  1. Connect one device only.
  2. Verify A, B and GND wiring.
  3. Verify baud rate, parity and stop bits.
  4. Verify the device address.
  5. Test Modbus communication.
  6. Add additional devices one at a time.
  7. Install termination as required.

Important: Refer to the product-specific Modbus register definition document for available commands and register addresses.

↑ Back to Application Notes


6. EMC Installation Guide for Motor Controllers

Motor controllers use high-frequency switching and can generate electromagnetic interference if wiring and installation are not designed correctly. Good EMC performance depends on the complete system, not only on the motor controller.

6.1 Keep Motor Wiring Short

Motor cables carry rapidly changing current and voltage. Keep them as short as practical.

Long motor cables can increase:

  • Radiated emissions
  • Conducted interference
  • Cable capacitance
  • Voltage transients

6.2 Separate Power and Signal Wiring

Keep motor and power cables physically separated from:

  • Analog control signals
  • Hall sensor wiring
  • Encoder wiring
  • RS-485 communication cables

Avoid long parallel runs between power and signal wiring.

6.3 Cross Cables at 90 Degrees

If signal and motor cables must cross, crossing at approximately 90 degrees can reduce electromagnetic coupling.

6.4 Use Twisted-Pair Wiring

Twisted pairs reduce loop area and improve immunity to external interference. They are especially useful for:

  • RS-485 communication
  • Hall signals
  • Encoder signals
  • Differential control signals

6.5 Shielding

Shielded cables may be required in electrically noisy environments. The shield should be connected according to the grounding concept of the complete machine or installation.

A shield is most effective when connected with a low-impedance connection rather than through a long thin wire.

6.6 Grounding and Bonding

Provide a low-impedance connection between conductive machine structures, enclosures and protective earth where required.

Poor grounding can contribute to:

  • Communication errors
  • Unstable analog signals
  • Unexpected resets
  • Increased EMC emissions

6.7 Power Supply Wiring

Keep the DC supply wiring sufficiently short and use conductor sizes suitable for the motor current.

High resistance or inductance in the supply wiring can contribute to:

  • Voltage drop during acceleration
  • Voltage transients during switching
  • Increased supply ripple

6.8 External Fuse

Install an external supply fuse according to the motor controller, wiring and application requirements.

The fuse primarily protects the supply wiring and system against excessive fault current.

6.9 Regenerative Energy

Power integrity problems can occur if regenerative energy causes the DC supply voltage to rise significantly.

Use a braking resistor or another suitable energy absorption method when required by the application and supported by the controller.

6.10 RS-485 and Signal Wiring

Communication and low-level signal cables should be routed separately from motor and braking resistor wiring.

For RS-485, use a twisted pair and correct bus termination.

Recommended Installation Layout

Wiring Type Recommendation
Motor cables Short, separated from signal wiring
Supply cables Short and correctly sized
Hall / Encoder Separated from motor wiring, twisted or shielded if required
Analog signals Keep away from switching power wiring
RS-485 Twisted pair, linear bus topology
Shield connections Low-impedance connection according to system grounding design

System-Level EMC Responsibility

Electromen motor controllers are components intended for integration into a complete machine or system.

The EMC performance of the final installation depends on the complete system, including:

  • Motor
  • Power supply
  • Cabling
  • Grounding and bonding
  • Enclosure
  • Other connected equipment

The system designer or integrator is responsible for verifying that the complete installation complies with the applicable EMC requirements.

Important: Always follow the product-specific installation instructions in addition to these general recommendations.

↑ Back to Application Notes


Important Information

These Application Notes provide general engineering guidance for Electromen motor controller applications. They do not replace the technical documentation of an individual product.

Electrical ratings, current limits, protection thresholds, I/O functions, parameter settings, braking resistor values and communication features vary between Electromen products.

Always refer to the product-specific datasheet, user manual and Modbus documentation before designing, installing or commissioning a system.

Electromen products are components intended for integration into a complete machine or system. The system designer or integrator is responsible for the correct application of the product and for compliance of the complete system with applicable electrical, EMC and safety requirements.

↑ Back to Application Notes

AAA - credit rating

ISO-certified suppliers and subcontractors

100% Finnish production chain

Device design, programming, and laboratory testing

Short delivery time

Back to top
Our website uses cookies to enhance user experience. You can adjust your preferences from the settings
1 Items in cart
Cart
Overall:
0,00€