EM-162A Power Controller

Key Features

  • Triac phase-angle controller for AC loads
  • Suitable for resistive and inductive loads
  • 0–10 V and 4–20 mA control inputs
  • Adjustable 0–25% base level
  • Galvanic isolation between the control and power stages
  • Integrated power-stage fuse
  • Control-stage overvoltage and reverse-polarity protection
  • Compact construction for automation applications

Overview

EM-162A is a triac phase-angle controller designed for controlling both resistive and inductive AC loads. Its advanced triggering technique provides reliable operation with loads such as lamps, resistive heaters, fan motors, and transformers.

The controller accepts either a 0–10 V or 4–20 mA analog control signal. An adjustable base level allows the minimum output level to be set between 0% and 25%.

Read more Show less

Load Control

The advanced triac triggering method enables the EM-162A to control both resistive and inductive loads. Typical applications include lighting, electric heating, fan speed control, and transformer control.

Base Level Adjustment

The adjustable base level can be used to set the minimum output level between 0% and 25%. This is particularly useful in lighting and fan applications where operation below a certain output level is not required or may cause unreliable startup.

Control Interface and Isolation

The control stage is galvanically isolated from the power stage with an isolation voltage of 1500 Vrms. This simplifies connection to automation systems and helps protect the low-voltage control circuitry from the mains-powered output stage.

The controller supports both 0–10 V voltage control and 4–20 mA current-loop control.

Protection

The power stage is protected by an integrated fuse. The control stage includes protection against overvoltage and reverse polarity.


Technical Data EM-162A

Supply voltage 190–265 VAC
Current consumption 1 A max.
Load 10–200 W
Control range 0–99%
Base level adjustment 0–25%
Auxiliary voltage 12–30 VDC
Auxiliary voltage current 20 mA max.
Control input 0–10 V / Rin 100 kΩ
Alternative control input 4–20 mA / Rin 180 Ω
Control start 100 mV / 4.2 mA
Fuse T1.6 A
Isolation voltage 1500 Vrms
Operating temperature −10…+50°C
Dimensions 90 × 60 × 36 mm
Weight Approx. 70 g

Tuotetiedostot

EN_em-162A.pdf (151,10 KB)
Varastosaldo: 17 kpl
53,00 €
VAT 0%

Ordering larger quantities +100pcs.

For volume discounts pls. see the Contact Info for Electromen distributors. If you didn´t find your country distributor then ask direct offer from office@electromen.com

AAA - credit rating

ISO-certified suppliers and subcontractors

100% Finnish production chain

Device design, programming, and laboratory testing

Short delivery time

Takaisin ylös
Sivustomme käyttää evästeitä käyttäjäkokemuksen parantamiseksi. Voit muuttaa eväste valintojasi asetuksista
1 Tuotetta ostoskorissa
Ostoskori
Yhteensä:
0,00€