EM-M82A Line guard

Key Features

  • Load control and line monitoring in a single unit
  • Suitable for loads with a terminal impedance of 15–300 Ω
  • Designed for solenoids, valves, contactors and resistive loads
  • Monitors load impedance in both energized and de-energized states
  • Automatic learning of normal line impedance
  • Separate learning of ON and OFF states for non-linear loads
  • Detection of open circuits, short circuits and abnormal impedance changes
  • Control relay monitoring through command and line-voltage comparison
  • Fail-safe fault relay
  • Self-resetting line protection
  • Integrated snubber circuit for inductive loads
  • Optional isolation between the control and load circuits

Overview

EM-M82A is a combined control and monitoring unit for automation devices with a terminal impedance between 15 and 300 Ω. Typical loads include solenoids, valves, contactors and resistive devices.

The unit controls the connected load through an internal relay while continuously monitoring the load circuit. It learns the normal line impedance and generates a fault alarm if the measured impedance changes outside the permitted range.

Read more Show less

Impedance Monitoring

The EM-M82A monitors the impedance of the connected load circuit in both the energized and de-energized states. Two selectable impedance ranges are available:

  • Range 1: 50–300 Ω
  • Range 2: 15–100 Ω

The measuring range is selected using the configuration switches. After selecting the appropriate range, the normal line impedance is stored by pressing the programming button.

A fault alarm is generated if the measured load resistance decreases by more than 50% or increases by more than 100% relative to the learned reference value.

Standard and Special Learning

In standard learning mode, the device learns the normal electrical characteristics of the connected load circuit.

For non-linear loads, a special learning procedure can be used. In this mode, the de-energized and energized states are learned separately, allowing the monitoring limits to be based on the normal characteristics of each operating state.

Control Relay Monitoring

The EM-M82A also monitors the operation of its internal control relay. The unit compares the control input state with the detected line voltage.

If the commanded state and the measured line condition do not correspond, the unit generates a fault alarm. This can help detect faults such as a control relay that does not operate as expected or an unexpected voltage condition on the load line.

Load Control

The load is switched through an internal control relay. The relay can control loads with a continuous current of up to 1.5 A.

An integrated snubber circuit is provided for switching inductive loads such as solenoids, valves and contactor coils.

Fault Output and Fail-Safe Operation

The fault output relay is energized during normal operation. When a monitored fault is detected, the relay is de-energized. Loss of the EM-M82A supply voltage therefore also produces a fault indication in the external monitoring system.

The alarm operates with an approximately one-second delay and resets automatically after the fault condition has been removed.

Protection and Isolation

The load line is protected by a self-resetting 1.8 A PTC device. The unit also includes protection against voltage transients on the load line and reverse polarity at the supply input.

The control connection can normally share the supply reference. If required, the control connection can be separated from the supply circuit to provide isolation between the control and load-side circuitry.


Technical Data EM-M82A

Supply voltage 18–35 VDC
Overvoltage limit 40 VDC
Idle current 30 mA
Recommended load impedance 15–300 Ω, depending on selected range
Load current, continuous Max. 1.5 A
Line protection 1.8 A self-resetting PTC
Sense current 3.3 mA or 10 mA
Sense resistor 1 Ω or 0.33 Ω
Control input resistance 1 kΩ (pins 1–2)
Control input, relay energized 18–35 VDC
Control input, relay released 0–3 V
Impedance range 1 50–300 Ω, Rs = 1 Ω, Is = 3.3 mA
Impedance range 2 15–100 Ω, Rs = 0.33 Ω, Is = 10 mA
Fault threshold Load resistance change below −50% or above +100%
Alarm delay 1 s
Alarm reset Automatic after the fault condition is removed
Alarm relay contact rating 1 A at 32 VDC
Isolation voltage 500 V when the control connection is separated
Stock: 50+ pcs.
115,00 €
VAT 0%

Ordering larger quantities +100pcs.

For volume discounts pls. see the Contact Info for Electromen distributors. If you didn´t find your country distributor then ask direct offer from office@electromen.com

AAA - credit rating

ISO-certified suppliers and subcontractors

100% Finnish production chain

Device design, programming, and laboratory testing

Short delivery time

Back to top
Our website uses cookies to enhance user experience. You can adjust your preferences from the settings
1 Items in cart
Cart
Overall:
0,00€