EM-M41-2 input isolator

Key Features

  • Optical isolation of 4–20 mA current-loop signals
  • Designed for PLCs and industrial control systems
  • 1:1 input-to-output current conversion
  • High 1500 V isolation rating
  • Extended current range from 1 to 22 mA
  • Wide 10–32 VDC operating range
  • Current-loop-powered input stage
  • Input overcurrent protection
  • Output overvoltage and reverse-polarity protection
  • DIN-rail-mountable housing
  • Available as a single- or dual-channel module

Overview

EM-M41 is an optical signal isolator designed for galvanic isolation of 4–20 mA current-loop signals in PLC and industrial control systems. It transfers the input current to the isolated output with a nominal 1:1 conversion ratio.

The module provides a specified isolation voltage of 1500 V and supports an extended signal range from 1 to 22 mA. The input stage obtains its operating energy from the current-loop signal, reducing the need for an additional input-side power connection.

Read more Show less

Current-Loop Isolation

The EM-M41 receives a 4–20 mA input signal and reproduces it as an electrically isolated output current. The nominal input-to-output conversion ratio is 1:1 with a specified ratio accuracy of ±0.1%.

The nominal signal range is 4–20 mA. The module can also operate over an extended current range from 1 to 22 mA, allowing signal levels outside the nominal process range to be transferred.

Optical Isolation

Optical signal transmission provides galvanic isolation between the input and output circuits. The specified isolation voltage is 1500 V.

The isolation helps prevent ground-loop currents and unwanted electrical coupling between field instrumentation and PLC or control-system inputs.

Dynamic Performance

The module transfers signals from DC up to 100 Hz. The specified 10–90% settling time is 10 ms, making the unit suitable for standard process signals and moderately changing measurement values.

Protection Functions

The input stage includes overcurrent protection. The output stage is protected against overvoltage and incorrect polarity.

Single- and Dual-Channel Versions

The standard EM-M41 provides one isolated signal channel in a DIN-rail-mountable housing.

A dual-channel version is available under the type code EM-M41-2. The two-channel version requires approximately 10 mm of installation width per channel.


Technical Data EM-M41

Operating voltage 10–32 VDC
Nominal signal range 4–20 mA
Extended operating range 1–22 mA
Current conversion ratio 1:1 (±0.1%)
Linearity error < 0.1%
Thermal drift < 100 ppm/°C
Input impedance 120 Ω
Input overcurrent protection 120 mA
Frequency range DC–100 Hz
10–90% settling time 10 ms
Isolation voltage 1500 V
Operating ambient temperature −10 … +60 °C
Dimensions (D × L × H) 20 × 79 × 75 mm
Weight 70 g
Mounting DIN rail
Dual-channel version EM-M41-2

Product files

EN_em-m41.pdf (47,03 KB)
Stock: 18 pcs.
104,00 €
VAT 0%

Ordering larger quantities +100pcs.

For volume discounts pls. see the Contact Info for Electromen distributors. If you didn´t find your country distributor then ask direct offer from office@electromen.com

AAA - credit rating

ISO-certified suppliers and subcontractors