EM-M25 TRMS

Key Features

  • True RMS measurement of AC voltage
  • Selectable measuring ranges up to 400 VAC
  • Converts AC voltage into an isolated 4–20 mA signal
  • Suitable for sinusoidal and non-sinusoidal waveforms
  • Galvanic isolation between the measured voltage and output circuit
  • Loop-powered operation without a separate auxiliary supply
  • Optional 1–5 V output using an external conversion resistor
  • Wide measuring-frequency range from 45 Hz to 1 kHz
  • Adjustable signal scaling
  • Protection against incorrect connections and voltage transients

Overview

EM-M25 is an isolated True RMS converter designed for measuring AC voltage and converting the measured value into a standard 4–20 mA process signal. Available measuring ranges cover AC voltages up to 400 VAC.

True RMS measurement allows the module to measure both sinusoidal and non-sinusoidal signals. The measurement circuit and output circuit are galvanically isolated, and the output side obtains its operating power from the current loop.

Read more Show less

True RMS Measurement

The EM-M25 measures the effective RMS value of an AC voltage. Unlike simple average-responding converters, True RMS measurement can also be used with non-sinusoidal waveforms within the specified operating limits.

The supported measuring-frequency range is 45 Hz to 1 kHz.

Selectable Measuring Ranges

The EM-M25 is available with measuring ranges up to 400 VAC. The source data identifies the following ranges:

  • 0–145 VAC
  • 0–230 VAC
  • 0–400 VAC

The required range is selected according to the device wiring and configuration.

Current-Loop Output

The measured AC voltage is converted into a 4–20 mA output signal. The output circuit is powered from a 12–32 VDC current loop, so no separate auxiliary supply is required.

With a 24 VDC loop supply, the specified loop resistance is up to 700 Ω.

1–5 V Output

The 4–20 mA output can also be converted into a 1–5 V signal by connecting a suitable resistor according to the connection diagram.

A 250 Ω conversion resistor produces a nominal voltage of 1 V at 4 mA and 5 V at 20 mA.

Signal Adjustment

The signal scaling can be adjusted from −30% to +20%. This allows the output span to be matched more closely to the required measuring range.

Isolation and Protection

The AC measuring circuit is galvanically isolated from the output-loop circuit. The specified isolation voltage is 1500 VAC.

The module includes protection against incorrect connections and voltage transients.


Technical Data EM-M25

Output-loop supply voltage 12–32 VDC
Measurement principle True RMS
AC measuring range 1 0–145 VAC
AC measuring range 2 0–230 VAC
AC measuring range 3 0–400 VAC
Current output 4–20 mA
Optional voltage output 1–5 V using a conversion resistor
Linearity error < 2% with a sinusoidal input
Thermal drift < 200 ppm/°C
Settling time 0.3 s
Measuring-frequency range 45–1000 Hz
Signal adjustment range −30 … +20%
Isolation voltage 1500 VAC
Maximum loop resistance 700 Ω with a 24 VDC loop supply
Operating ambient temperature 0 … +60 °C

Product files

EN_em-m25.pdf (49,39 KB)
Stock: 50+ pcs.
75,00 €
VAT 0%

Ordering larger quantities +100pcs.

For volume discounts pls. see the Contact Info for Electromen distributors. If you didn´t find your country distributor then ask direct offer from office@electromen.com

AAA - credit rating

ISO-certified suppliers and subcontractors

100% Finnish production chain

Device design, programming, and laboratory testing

Short delivery time

Back to top
Our website uses cookies to enhance user experience. You can adjust your preferences from the settings
1 Items in cart
Cart
Overall: