EM-M24 conditioning amplifier provides complete galvanic isolation between input, output and supply. Frequency ranges are DIP-switch settable. Input and output ranges can be selected individually. Input filtering can be selected from two alternatives. The effect of zero and gain adjustments is ± 15 % of the selected range. Zero and gain adjustments have no mutual effect. The output of the amplifier is short-circuit protected and the operating voltage input is protected against incorrect polarity.
| TECHNICAL DATA | |
|---|---|
| Supply | 20...32 Vdc |
| Current Requirement | 60 mA max. |
| Linearity Error | < 0.1 % |
| Thermal Drift | < 60 ppm/°C |
| Signal Ranges | Rin |
| -10...+10 V | 1 Mohm |
| 0...+10 V | 500 kohm |
| -5...+5 V | 500 kohm |
| -1...+1 V | 100 kohm |
| 0...+1 V | 50 kohm |
| -20...+20 mA | 50 ohm |
| 0...+20 mA | 50 ohm |